CF800X series conventional fire alarm control panel supports 1/2/4 zones and 3 groups of sounders. Each zone can connect up to 50 smoke detectors, heat detectors, manual call points,etc. All zones and sounders of the fire alarm system can be disabled. All input and output devices are monitored by the control panel, and the control panel will automatically disconnect when the zones or sounders are short. The control panel can provide 24VDC / 300mA power for products that require an additional 24V power supply. The detailed status indicators clearly show the working status of the control panel and provide the first fire alarm and subsequent fire alarm functions. After the control panel sends a fire alarm signal, it can provide up to 120 seconds delay time to confirm whether thereis a real fire alarm. In addition, the control panel also provides the mains-lost silence function. After configure the mains-lost silence mode, the control panel will no longer send a fault signal to remind the user when the main power is lost.
Product Description
Specification:
Product Name: | Fire Alarm Control Panel | Main power supply: | AC220V± 15%,50Hz/ AC110V± 15%,60Hz |
Battery power supply: | DC 24V (2 x 12V 3.3Ah) | Product capacity: | 2 loops*254 points = 508 points |
Zone capacity: | Each zone has a maximum capacity of 50 devices. | Direct output: | 6 groups of wet contacts relay output. |
Contacts capacity : | 1A/24VDC, output current 500mA. | Battery power output: | 1 group 24V power output Output |
capacity: | 1A/24V. | Operating Environment: | Temperature -10°C~+50°C Humidity ≤95%. |
Dimensions: | 450mm×370mm×120mm. | Product standard: | GB4717-2005, GB16806-200. |
Dimension (Unit:mm)
Main Function:
1 System self-test
The system will test indicator light,LCD screen,sound and so on.
2 Inquiry function
You can see the device type, zone number, definition about whether there are devices, position information corresponding to each address in the loop.
3 Event record
Under this menu, you can see the fire alarm information and other operation record.
4 Data sampling
Data sampling can sample the products in the loop, and displayed as data. The data can be used to judge the status of the products.
5 Setting function
In this function, you can set the password, time and the printer.6 Installation and program functions
(1) Address coding: the control unit can read or write the product address.
(2)Login: Connecting the products to the control unit. Auto login can login the address and type of the products.
(3)Logic programming: Set the logical relationship between the product and the control unit. Including system linkage, bus linkage and direct linkage.
7 Feedback function
The control unit will display the feedback information after start the equipment manually or automatically and send the alarm sound, lights up the feedback light. Feedback is real information about the starting of fire-fighting equipment.
8 Faulty alarm function
The control unit can automatically check the working status of main power supply,battery power supply detectors and modules. If the control unit found any abnormal address during the inspection process, after many confirmations, it immediately reported the fault information of the control unit number, loop number, and address number. The "faulty" indicator light is on, and you can hear the faulty sound. Press the "mute" key to mute.