Sentek JB-TBL-8600 fire alarm control unit and fir e detectors and modules constitute an automatic monitoring and control system to monitor the fire smoke situation on the site, it uses intelligent algorithms to judge its status (fire alarm or fault or feedback) and accomplish automatic fire alarm and logic function. The control unit uses bus communication to set alarm, monitor and control on the same loop bus. The hardware circuit is controlled by a single chip microcomputer. The layout is simple and compact, and it is easy to install and expand. The control unit is wall-mounted, full English and Chinese LCDMain power supply: display with beautiful appearance, it is a high performance, high-reliability and intelligent fire alarm control unit.
Product Description
Specification:
Product Name: | Analogue Addressable Fire Alarm Control Panel | Main power supply: | AC220V± 15%, 50HZ. |
Battery power supply: | DC 24V (2 sealed batteries: 2*12V*4Ah) | Product capacity: | 2 loops*254 points = 508 points |
Loop capacity: | Up to 254 points in any combination of 2-wire smart smoke detector, heat detector, call point, input module,output module and sounder. |
Direct output: | 6 groups of wet contacts relay output. |
Contacts capacity : | 1A/24VDC, output current 500mA. | Battery power output: | 1 group 24V power output Output |
capacity: | 1A/24V. | Operating Environment: | Temperature -10°C~+50°C Humidity ≤95%. |
Dimensions: | 450mm×370mm×120mm. | Product standard: | GB4717-2005, GB16806-200. |
Dimension (Unit:mm)
Main Function:
1 System self-test
The system will test indicator light,LCD screen,sound and so on.
2 Inquiry function
You can see the device type, zone number, definition about whether there are devices, position information corresponding to each address in the loop.
3 Event record
Under this menu, you can see the fire alarm information and other operation record.
4 Data sampling
Data sampling can sample the products in the loop, and displayed as data. The data can be used to judge the status of the products.
5 Setting function
In this function, you can set the password, time and the printer.6 Installation and program functions
(1) Address coding: the control unit can read or write the product address.
(2)Login: Connecting the products to the control unit. Auto login can login the address and type of the products.
(3)Logic programming: Set the logical relationship between the product and the control unit. Including system linkage, bus linkage and direct linkage.
7 Feedback function
The control unit will display the feedback information after start the equipment manually or automatically and send the alarm sound, lights up the feedback light. Feedback is real information about the starting of fire-fighting equipment.
8 Faulty alarm function
The control unit can automatically check the working status of main power supply,battery power supply detectors and modules. If the control unit found any abnormal address during the inspection process, after many confirmations, it immediately reported the fault information of the control unit number, loop number, and address number. The "faulty" indicator light is on, and you can hear the faulty sound. Press the "mute" key to mute.