Conventional Fixed Temperature Relay Output Heat Detector

Product Details
Customization: Available
Type: Heat Detector
Usage: Temperature
Still deciding? Get samples of $ !
Request Sample

360° Virtual Tour

Diamond Member Since 2010

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
121
Year of Establishment
2005-11-14
  • Conventional Fixed Temperature Relay Output Heat Detector
  • Conventional Fixed Temperature Relay Output Heat Detector
  • Conventional Fixed Temperature Relay Output Heat Detector
  • Conventional Fixed Temperature Relay Output Heat Detector
  • Conventional Fixed Temperature Relay Output Heat Detector
Find Similar Products

Basic Info.

Model NO.
HD751
Installation Mode
Ceiling Mounted
Certification
CE, ISO, RoHS, UL En54
Application
Home, Industry
Wire
2 or 4 Wire Heat Detector
Warranty
5 Year Limted Warranty
Ceiling Spacing
40-50 Foot Rating for Heat Sensor
Alarm Indicator
LED Continuously Emitting Red Light
Temperature Range
-10 to 50
Humidity
0 to 95% Rh, No Condensation or Icing
Dimensions
100mm (Dia) X 46mm (Ht) with Base
Weight
120g/Set with Base
Transport Package
1PC/Box, 100PCS/Carton
Specification
UL, EN54, CE, ROSH
Trademark
SENTEK
Origin
China Ningbo
HS Code
8531100000
Production Capacity
60000/Month

Product Description

Conventional Fixed Temperature Relay Output Heat Detector
Conventional Fixed Temperature Relay Output Heat Detector

All of the Sentek's HD751 series detectors meet the requirements of UL521 and EN 54-5 for use in fi re alarm signaling systems, which provide fast and reliable response for heat 57°C (135°F) or Rate-of-Rise detection, They are intended for use in 2-wire/4-wire Class A2 supervised zone circuits.
The HD751 series detectors are subject to panel compatibility limits and compliance with corresponding NFPA 72 standards, localcodes, and ordinances.
Specification:

Response Temperature
  57°C (135°F)
  Ceiling Spacing:   50 foot rating for heat sensor
  Reset Voltage:   less than 1 volt
  Alarm Indicator:   LED continuously emitting red light
  Remote Output:   25 mA max., diode gate
  Temperature Range:   -10°C to 50°C
  Permissible Current:   80mA maximum
  Humidity:   0 to 95% RH, no condensation or icing
  Alarm Contact:   (for 4-wire) NO or NC Operation, Form A: 1.0A@30VDC/0.5A@125VAC
  Dimensions:   102mm (dia) x 43mm (ht) with base
  Weight:   125g/set with base
Conventional Fixed Temperature Relay Output Heat Detector
Conventional Fixed Temperature Relay Output Heat Detector


Product Features:
 2 or 4 wire models
 Advanced detection and discrimination algorithms
 Easy installation and maintenance
Sleek low-profi le housing design
Durable sensor head, no need for replacement
SMD circuit board design-satisfactory quality and reliability guaranteed
N/C (normal/close)-N/O (normal/open)selectable relay output
AR (Auto Reset) function for security systems (optional for 4 wire models) Sensor base option: standard and Shottky Diode
Five-year limited warranty
 
The range includes:
HD751-2 2 wire heat alarm
HD751-2L 2 wire heat alarm with remote LED output
HD751-4 4 wire heat alarm (12/24VDC)
HD751-4B 4 wire heat alarm with buzzer (12/24VDC)
HD751-4AR 4 wire heat alarm with auto-reset function (12/24VDC)
HD751-4ARB 4 wire heat alarm with auto-reset function and buzzer (12/24VDC)
Related Products
Conventional Fixed Temperature Relay Output Heat Detector
Conventional Fixed Temperature Relay Output Heat Detector

Company Information
Conventional Fixed Temperature Relay Output Heat Detector

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier