Specification:
Product Name: | Fire Detection Alarm System | Main power supply: | AC220V± 15%,50Hz/ AC110V± 15%,60Hz |
Battery power supply: | DC 24V (2 x 12V 3.3Ah) | Product capacity: | 1/2/4 zone |
Zone capacity: | Each zone up to 50 pcs smoke detector, heat detector, call point, input module,output module,sounder. ext. | Sounder alarm output | 3 x 300mA (max)/24VDC |
Zone and sounder end of line resistors: | 3.9KΩ,1W | Zone monitoring current: | <4.5mA |
Zone alarm current: | >20mA | Humidity: | ≤95%RH |
Dimensions: | 290 x 87.5 x 211.5mm | weight: | 2100g (without battery) |
Fire Detection Alarm System
Main functions:
• The CF800X panel is available on 1,2,4 zones.
• Each zone has a maximum capacity of 50 devices.
• It has 3 groups of sounders output circuits each capable of supplying 300mA.
• It has a 24V/300mA auxiliary supply.
• It has a set of fault relay contacts,rated at 0.5A SELV.
• It has the ability to disable any zone,any group of sounder.
• The panel will send a fault signal when there is zone short/open or sounder short/open.
• It has the ability to disconnect the zones and sounders automatically when there is zone short or sounder short.
After the short is clear, the zones and sounders will recover.
• It has the sounder start/stop and delay facility (the delay time is 30-120 seconds in 30 seconds increments).
• It has the "rst "re alarm and subsequent "re alarm functions.
The indicator of the "rst "re zone is #ashing and the subsequent"re zone is lit.
• It has the mains-lost silence function.After con"gure the mains lostsilence function,the panel will not send the main power lost fault signal.