Customization: | Available |
---|---|
Type: | Home Alarm |
Signal Transmission: | Wired Alarm |
Still deciding? Get samples of US$ 7.5/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Specification:
Smoke Sensitivity: | 0.98~4%/FT Obsuration(UL standard) |
Ceiling Spacing: | 50 foot rating for heat sensor (55 degree) |
Reset Voltage: | less than 1 volt |
Reset Time: | less than 1 second |
Alarm Indicator: | LED continuously emitting red light |
Remote Output: | 25 mA max., diode gate |
Temperature Range: | -10°C to 55°C,UL268 temperature 0~37.8 °C |
Permissible Current: | 80mA maximum |
Humidity: | 0 to 95% RH, no condensation or icing |
Alarm Contact: | (for 4-wire)NO or NC Operation, Form A: 1.0A@30VDC/0.5A@125VAC |
Dimensions: | 100mm (dia) x 46mm (ht) with base |
Weight: | 130g/set with base |
Sentek Smoke Detector SD119 with UL/En54 Approved
Product Features:
Order Information:
SD119-2: 2 wire photoelectric smoke alarm
SD119-2-LED: 2 wire photoelectric smoke alarm with remote LED output
SD119-2H: 2 wire photoelectric smoke and heat alarm
SD119-2H-LED: 2 wire photoelectric smoke and heat alarm with remote LED output
SD119-4: 4 wire photoelectric smoke alarm(12/24/48VDC)
SD119-4B: 4 wire photoelectric smoke alarm with Buzzer(12/24/48VDC)
SD119-4AR: 4 wire photoelectric smoke alarm with auto-reset function(12/24/48VDC)
SD119-4ARB: 4 wire photoelectric smoke alarm with auto-reset function and Buzzer(12/24/48VDC)
SD119-4H: 4 wire photoelectric smoke and heat alarm (12/24/48VDC)
SD119-4HB: 4 wire photoelectric smoke and heat alarm with Buzzer(12/24/48VDC)
SD119-4HAR: 4 wire photoelectric smoke and heat alarm with auto-reset function(12/24/48VDC)
Model |
2/4 Wire |
Heat Sensor Setting |
Voltage DC (Min./MAX.) |
Standby Current (Max.) |
Alarm Current (12/24V) |
Surge Current (Max.) |
Start-Up Time (Max.) |
Permissible Current (Max.) |
Cycle Time | Alarm Contact | Certified |
SD119-2 | 2 | 10.8-33V | 80µA | 22/55mA | 160µA | 30Sec. | 80mA | 1-3Sec. | - | UL/EN | |
SD119-2L | 2 | 10.8-33V | 80µA | 22/55mA | 160µA | 30Sec. | 80mA | 1-3Sec. | Remote LED | UL/EN | |
SD119-2H | 2 | 135±5°F | 10.8-33V | 80µA | 22/55mA | 160µA | 30Sec. | 80mA | 1-3Sec. | - | UL/EN |
SD119-2HL | 2 | 135±5°F | 10.8-33V | 80µA | 22/55mA | 160µA | 30Sec. | 80mA | 1-3Sec. | Remote LED | UL/EN |
SD119-4-12/24 | 4 | 12/24V | 80µA | 30/45mA | - | 30Sec. | - | 1-3Sec. | Form A | UL/EN | |
SD119-4H-12/24 | 4 | 135±5°F | 12/24V | 80µA | 30/45mA | - | 30Sec. | - | 1-3Sec. | Form A | UL/EN |
SD119-4AR-12/24 | 4 | 12/24V | 100µA | 30/45mA | - | 30Sec. | - | 1-3Sec. |
Form A Auto Reset |
CE | |
SD119-4ARB-12/24 | 4 | 12/24V | 100µA | 30/45mA | - | 30Sec. | - | 1-3Sec. |
Form A Auto Reset |
CE | |
SD119-4B-12/24 | 4 | 12/24V | 80µA | 30/45mA | - | 30Sec. | - | 1-3Sec. | Form A | CE | |
SD119-4HB-12/24 | 4 | 135±5°F | 12/24V | 80µA | 30/45mA | - | 30Sec. | - | 1-3Sec. | Form A | CE |
SD119-4HARB-12/24 | 4 | 135±5°F | 12/24V | 100µA | 30/45mA | - | 30Sec. | - | 1-3Sec. |
Form A Auto Reset |
CE |
Company Information